Research · Bavaria, Germany
Electron microscopy suite in a research institute
1.8 µT → 45 nT
01 · Challenge
Image drift on a new TEM caused by a tram line 60 m away and by building service currents.
02 · Simulation
Source separation via synchronised long-term measurement plus a simulation of the room enclosure and residual DC transients.
03 · Solution
A mu-metal room enclosure with active compensation coils for the tram's variable DC component.
04 · Execution
Installed during a scheduled instrument shutdown, followed by joint acceptance testing with the manufacturer.
05 · Result
Residual field below 45 nT peak-to-peak — inside the vendor's specification with margin.
Start a project
Tell us the field level you need. We will tell you how to reach it.
A first assessment by one of our engineers is free of charge and usually takes less than 48 hours.
